Performonce of Fouling Fluidized-Removing and Heat Transfer Enhancement on Sewage Side of Sewage-Source Heat Pump System
High thermal resistance resulted by fouling in heat exchanger restricts the application of sewage source heat pump (SSHP) system. The fouling forming mechanism was applied with solid-liquid fluidized bed technique for fouling prevention and removing of SSHP system. Shearing stress model of solid-liquid fluidized bed heat-exchanger is analyzed
and collision stress model is modified. Preventing and removing fouling mechanisms of solid-liquid fluidized bed technique by shearing stress and collision stress was explained. An experimental study on how to solve the fouling problem (such as fouling prevention and removing
heat transfer enhancement
etc) is discussed. The results of theory and experiment show that solid-liquid fluidized bed technique can be used not only to increase convection coefficient
but also to restrict fouling growing
it can effectively solve the fouling problem in SSHP system.