XUAN Yongmei, WANG Hailiang, HUANG Xiang. Operational Parameters of Hybrid Radiant Cooling Floor and Displacement Ventilation Air Conditioning System[J]. Journal of Civil and Environmental Engineering, 2012, 34(6): 115-119.
DOI:
XUAN Yongmei, WANG Hailiang, HUANG Xiang. Operational Parameters of Hybrid Radiant Cooling Floor and Displacement Ventilation Air Conditioning System[J]. Journal of Civil and Environmental Engineering, 2012, 34(6): 115-119. DOI: 10.3969/j.issn.1674-4764.2012.06.019.
Operational Parameters of Hybrid Radiant Cooling Floor and Displacement Ventilation Air Conditioning System
The simulation model of hybrid radiant cooling floor and displacement ventilation air conditioning system was built and analyzed by software EnergyPlus. By comparing the simulation results and experimental data
it is shown that the simulated indoor air temperature and cooling capacity provided by radiant floor was ±7% deviated from the experimental data. Based on the model
with the change of supply air parameters or supply water parameters
the cooling capacity provided by radiant floor and displacement ventilation
surface temperature of radiant floor
indoor air average temperature
AUST temperature were obtained. Combined with the indoor thermal comfort model
when indoor thermal comfort index PMV varied between -0.5 and 0.5
the recommended supply air and supply water parameters were obtained to provide reference for engineering design and application.