AN EXPERIMENTAL RESEARCH ON ENHANCEMENT OF HEAT TRANSFER OF FINNED TUBES IN REFRIGERANT HEAT EXCHANGER[J]. Journal of Civil and Environmental Engineering, 1995, 17(2): 45-51.
AN EXPERIMENTAL RESEARCH ON ENHANCEMENT OF HEAT TRANSFER OF FINNED TUBES IN REFRIGERANT HEAT EXCHANGER[J]. Journal of Civil and Environmental Engineering, 1995, 17(2): 45-51. DOI: 10.11835/j.issn.1674-4764.1995.02.007.
the comparative experimental research that air flows through theout-surface of a single row finned tubes is done in a drawing wind tunnel and the three differnetshapes of rectangluar finned tubes are compared with a plain finned tube that is usually used in therefrigerant heat exchanger
the useful results are obtained. The results show that
in the range ofwind velocity flowing through the marrowest area
W_(max)=2.5m/s to 8.5m/s
the average convec-tion heat transfer coefficient of the two-side V-groove finned tube is higher than that of rectangluarplain finned tube
It is a new type finned tube that has good heat transfer performance and it isworth poplarlzing.