1. 重庆大学,三峡库区生态环境教育部重点实验室,重庆,400045
2. 中铁第四勘查设计院集团有限公司,武汉,430063
纸质出版:2010
移动端阅览
高亚锋, 李百战, 陈玉远, 等. 一次泵空调冷水系统的水力特性与节能分析[J]. 土木与环境工程学报(中英文), 2010,32(6):100-104.
GAO Ya-feng, LI Bai-zhan, CHEN Yu-yuan, et al. Hydraulic Characteristics and Energy Efficiency of An Air Conditioning Chilled Water System With Primary Pumps[J]. Journal of Civil and Environmental Engineering, 2010, 32(6): 100-104.
高亚锋, 李百战, 陈玉远, 等. 一次泵空调冷水系统的水力特性与节能分析[J]. 土木与环境工程学报(中英文), 2010,32(6):100-104. DOI: 10.11835/j.issn.1674-4764.2010.06.017.
GAO Ya-feng, LI Bai-zhan, CHEN Yu-yuan, et al. Hydraulic Characteristics and Energy Efficiency of An Air Conditioning Chilled Water System With Primary Pumps[J]. Journal of Civil and Environmental Engineering, 2010, 32(6): 100-104. DOI: 10.11835/j.issn.1674-4764.2010.06.017.
以一次泵空调冷水系统为研究对象,针对其水力特性与节能方式进行了理论分析。结果表明:末端为空调机的一次泵水系统易出现大温差小流量的情况,而末端为空调机与风机盘管组合形式的系统易出现小温差大流量情况。在冷负荷减少时,为更好的确保一次泵空调冷水系统节能运行,采用定水量系统调节冷水机组出口水温时应减少水系统的旁通水量;采用水泵变频调节且水泵所占空调水系统能耗比大于0.3,当系统的水力特性越接近末端为空调机形式的水力特性时,采用水泵变频调节效果越好(节能率大于10%)。在采用调节冷水机出水温度和变频调节冷水量匹配冷负荷时,冷水过量情况仍然存在,需旁通水量,水泵定频和变频时,可分别根据单台冷水机水流量的1.2~1.8、0.2~1倍来选择旁通管径。
The hydraulic characteristics and energy-saving performance of a chilled water system with primary pumps is analyzed. It is proved that the hydraulic characteristics of the system with terminal of the air conditioners tends to large temperature differences and small flow rate
while the hydraulic characteristics of the system with terminal of the combination of fan coil units and air conditioners tends to large flow rate and small temperature differences. When the cooling load is reduced
in order to ensure the energy-saving performance of the primary pump system
the fixed chilled water flow is required. If the fixed water flow system is adopted to regulate the outlet water temperature,the bypass water flow rate should be decreased as much as possible. If the pump frequency regulation is selected
and the proportion of energy consumption of the pump accounts for 30% of the total at the same time
the more the system’s hydraulic characteristics approaches that of air conditioners
the higher the energy-saving rate will be
which could be markedly greater than 10%. By regulating the water temperature and cold water quantity
over flow of chilled water still exists. Therefore
bypass water flow should be provided. And the bypass pipe diameter is determined respectively by the water flows which are 1.2 ~ 1.8 or 0.2 ~ 1.0 times larger than that of a single chiller when the pump works in frequency conversion and constant frequency.
0
浏览量
982
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构