DONG Jian kai, JIANG Yi qiang, YAO Yang, et al. Experimental Analysis on Characteristics of Energy Storage for Defrosting of Air Source Heat Pump with Phase Change Energy Storage[J]. Journal of Civil and Environmental Engineering, 2011, 33(2): 74-79.
DONG Jian kai, JIANG Yi qiang, YAO Yang, et al. Experimental Analysis on Characteristics of Energy Storage for Defrosting of Air Source Heat Pump with Phase Change Energy Storage[J]. Journal of Civil and Environmental Engineering, 2011, 33(2): 74-79. DOI: 10.11835/j.issn.1674-4764.2011.02.015.
The performances of energy storage modes are experimentally analyzed in the artificial environment in order to study the effect of energy storage modes for defrosting of air source heat pump with phase change energy storage. Results indicate that suction and discharge pressures are stable at 038 MPa and 165 MPa under the series energy storage mode
and suction and discharge temperatures are 6.9℃ and 75.0℃ respectively. However
the suction and discharge pressures are as low as 012 MPa and 116 MPa in parallel and single energy storage modes individually
and the discharge temperature is up to 1225℃. In addition
in series energy storage mode
the phase change material can completely change from solid to liquid in energy storage process. The temperature difference is about 18.0℃ for indoor coil
and the input power to compressor is 825W. Therefore
the system pressures and temperatures are most stable in the series energy storage mode and the time for energy storage is short