Sharing Rate of Cooling Load of Radiant Terminal Device and Air Supply Terminal Device in Residential Buildings——From the Perspective of Thermal Comfort and Indoor Air Quality
SUI Xue-min, ZHANG Xu. Sharing Rate of Cooling Load of Radiant Terminal Device and Air Supply Terminal Device in Residential Buildings——From the Perspective of Thermal Comfort and Indoor Air Quality[J]. Journal of Civil and Environmental Engineering, 2011, 33(5): 114-120.
SUI Xue-min, ZHANG Xu. Sharing Rate of Cooling Load of Radiant Terminal Device and Air Supply Terminal Device in Residential Buildings——From the Perspective of Thermal Comfort and Indoor Air Quality[J]. Journal of Civil and Environmental Engineering, 2011, 33(5): 114-120. DOI: 10.11835/j.issn.1674-4764.2011.05.019.
for three different residential load types such as low load
medium load
and high load type
indoor thermal environments of different load sharing-rates are simulated
respectively. Indoor thermal comfort and indoor air quality of different load sharing-rates are also analyzed and evaluated. And the appropriate range of cooling load sharing-rates are given from the view of both occupants thermal comfort and occupants health. When ωc (the sensible heat load sharing rate of the radiant terminal device) <0.7
the human thermal index in work region can be controlled within the range of thermal comfort standard. From the point of avoiding local discomfort
ωc is suggested to take 04~1. As regard to indoor air quality
for the constant air volume mode
ωc is suggested to take 0.5~0.9 under low and middle load conditions
and ωc is suggested to take 0.35~0.6 under high load conditions. For the variable air volume mode